Definition: Set of moving device that fitted into a closed conduit driven directly by water flow. Its turbine rotor rotates about the axis which is perpendicular to water flow.
Working principles: Water flow drives vane rotate. Rotating times which is proportional to water flow speed are gathered, hence total volume passed through water meter is recorded.
Characters:
Types: Wet, dry, vertical, liquid sealed.
Wide measuring range, high accuracy.
Stable measuring capacity
Long working life
Low pressure loss
All technical figures are conformed with GB/t778.1~3-1996 which is equivalent to ISO4064 standard class c.
Working condition:
Water temperature≤ 50ºC(hot water meter≤ 90ºC)
Water pressure≤ 1mpa
Maximum permissible error:
From the minimum flow-rate (qmin) inclusive to the lower zone of the transitionalflow-rate (qt) exclusive: ± 5%.
From the transitional flow-rate (qt) inclusive to the higher zone of the maximum flow-rate (qmax) exclusive: ± 2%(hot water meter± 3%. )
Size | Class of Measurement | Overload Flow-rate Qs(m³/h) | Permanent Flow-rate Qp(m³/h) | Transitional flow-rate Qt(l/h) | Minimun flow-rate Qmin(l/h) |
DN15 | C | 3 | 1.5 | 22.5 | 15 |
DN20 | C | 5 | 2.5 | 37.5 | 25 |